by homerjon_mistaway | Dec 31, 1969 | Gen 1.3 - Troubleshooting, Gen 3 - Troubleshooting
Potential Causes: System Mode is set to OFF or REM (or ON) and should be set to AUTO EVERYDAY or AUTO-CUSTOM. See Controller: Setting System Mode There are no AUTO MIST cycles defined. See Controller: Setting AUTO MIST Cycles The controller has calculated that the...
by homerjon_mistaway | Dec 31, 1969 | Controller & Remote, Gen 1.3 - Troubleshooting, Gen 3 - Troubleshooting
Unit displays NOZ00 and will not mist. Cause: Nozzle count in the SET-Up Menu is not set. Clear by pressing and holding the Red MENU/STOP button for 5 seconds. Press the Red MENU/STOP button to display the triangular cursor, ►, by DAY/TIME position on left side of...
by homerjon_mistaway | Dec 31, 1969 | Gen 1.3 - Troubleshooting
See Gen 1.3: Controller displays “MIST”, but Nozzles Not Misting 1. Remove drum lid and confirm liquid level in drum is at or above intake filter and that filter is clean If liquid level is low, add water. If filter is clogged, clean and replace. Run...
by homerjon_mistaway | Dec 31, 1969 | Gen 1.3 - Troubleshooting
Displayed Level is greater than Actual Level Possible Causes: Actual flow rate is greater than the controller Target Flow Rate (NFR entered into the DATA Menu) – which may also point to a leak or siphon in the nozzle circuit. Actual nozzle count is greater than...
by homerjon_mistaway | Dec 31, 1969 | Gen 1.3 - Troubleshooting
What is ERR3: ERR3 is displayed when the actual MIST volume is significantly greater than the target volume. Most Common Cause: leak in the nozzle circuit. Other Potential Causes: There are more nozzles installed in the nozzle circuit than entered as the NOZ count in...